Modbus Protocol

This device communicates using the Modbus RTU protocol over the RS-485 standard.

Device Address

This device's preconfigured user-definable address is 0x17. Users can change the address using the holding registers.

Modbus Function Codes

The following Modbus function codes are functional with this device.

Command Register
Function
Description
Bytes

0x03

Read holding registers

Returns configuration parameters

2

0x04

Read input registers

Returns measured readings and statistics

2

0x06

Write single register

Writes a single configuration parameter

2

0x10

Write multiple registers

Writes multiple configuration parameters

2 x N

Device Registers

The following registers are available with this device.

Register Type
Register Address
Description
Bytes

Input Register (R)

0x0001

Irradiance (Actual)

2

Input Register (R)

0x0002

Irradiance (Average)

2

Input Register (R)

0x0003

Irradiance (Min)

2

Input Register (R)

0x0004

Irradiance (Max)

2

Input Register (R)

0x0005

Irradiance (Std. Dev.)

2

Input Register (R)

0x0006

Panel Temperature (Actual)

2

Input Register (R)

0x0007

Panel Temperature (Average)

2

Input Register (R)

0x0008

Panel Temperature (Min)

2

Input Register (R)

0x0009

Panel Temperature (Max)

2

Input Register (R)

0x000A

Panel Temperature (Std. Dev.)

2

Input Register (R)

0x000B

Device Pitch (Actual)

2

Input Register (R)

0x000C

Device Roll (Actual)

2

Input Register (R)

0x000D

Device Temperature

2

Holding Register (R/W)

0x0101

Device Address

2

Holding Register (R/W)

0x0102

Baud Rate

2

Holding Register (R/W)

0x0103

Statistics Period (Secs)

2

Holding Register (R/W)

0x0104

IMU Correction (Pitch)

2

Holding Register (R/W)

0x0105

IMU Correction (Roll)

2

Holding Register (R/W)

0x0106

Irradiance Correction 1

2

Holding Register (R/W)

0x0107

Irradiance Correction 2

2

Holding Register (R/W)

0x0108

Irradiance Correction 3

2

Holding Register (R/W)

0x0109

Temperature Correction

2

Communication Syntax

Reading sensor data

The host device can read one or more sensor data by calling the starting register address.

Request from the host: Device address [1 Byte] + Function code (0x04) [1 Byte] + Input register start address [2 Bytes MSB first] + Requested register length [2 Bytes MSB first] + CRC [2 Bytes MSB first]

Response from the device: Device address [1 Byte] + Function code (0x04) [1 Byte] + Response register length in Bytes [1 Byte] + Register 1 [2 Bytes MSB first] + Register N [2 Bytes MSB first] + CRC [2 Bytes MSB first]

Reading configuration register

The host device can read one or more configuration registers by calling the starting register address.

Request from the host: Device address [1 Byte] + Function code (0x03) [1 Byte] + Holding register start address [2 Bytes MSB first] + Requested register length [2 Bytes MSB first] + CRC [2 Bytes MSB first]

Response from the device: Device address [1 Byte] + Function code (0x03) [1 Byte] + Response register length in Bytes [1 Byte], Register 1 [2 Bytes MSB first] + Register N [2 Bytes MSB first] + CRC [2 Bytes MSB first]

Writing single configuration register

The host device can write one configuration register.

Command from the host: Device address [1 Byte] + Function code (0x06) [1 Byte] + Holding register address [2 Bytes MSB first] + Value to be set [2 Bytes MSB first] + CRC [2 Bytes MSB first]

Response from the device: Device address [1 Byte] + Function code (0x06) [1 Byte] + Holding register address [1 Byte] + Value set [2 Bytes MSB first] + CRC [2 Bytes MSB first]

Writing multiple configuration registers

The host device can write multiple configuration registers.

Command from the host: Device address [1 Byte] + Function code (0x10) [1 Byte] + Holding register start address [2 Bytes MSB first] + Requested register length [2 Bytes] + Configuration values length in Bytes [1 Byte] + Value to be set 1 [2 Bytes MSB first] + Value to be set N [2 Bytes MSB first] + CRC [2 Bytes MSB first]

Response from the device: Device address [1 Byte] + Function code (0x10) [1 Byte] + Holding register start address [1 Byte], Value set [2 Bytes MSB first], CRC [2 Bytes MSB first]

Last updated